National Grid Code of Mauritius — Distribution Code, Version December 2022
The purpose of the Distribution Code is to establish the rules, procedures, requirements and standards governing the operation, maintenance and development of the Distribution System in order to ensure an efficient, coordinated and economic electricity distribution system. It also defines the procedures and requirements applicable to the Distribution Licensee and all Users of the Distribution System.
The Distribution Licensee as well as existing and potential Users connected to or seeking to connect to the Distribution System shall comply with the relevant sections of the Distribution Code, including Distributed Generators and Customers. Users connected to the Distribution System shall comply with the Distribution Code. The Interconnection Boundary between the Transmission and Distribution Systems shall be as defined in Section TC 1.1 of the Transmission Code.
This Distribution Code contains the procedures for providing an adequate, safe and efficient electricity distribution service to all regions of Mauritius, taking into account a wide range of Normal and Contingency Conditions. When unforeseen situations arise, the Distribution Licensee shall act as a reasonable and prudent operator in pursuit of one or more of the following general requirements:
Users shall provide the reasonable cooperation and assistance that the System Operator reasonably requests in pursuit of the general requirements of this Section DC 2.
The Distribution Licensee together with the Single Buyer shall be responsible for planning the development of the Distribution System. The Authority shall provide Ministerial policy guidelines for system development. The Single Buyer shall develop procedures for the elaboration of a long-term Integrated Resource Plan (IRP) (10-year horizon, updated annually), involving key stakeholders in a collaborative process. The Distribution Licensee and the Transmission Licensee shall be responsible for implementing the upgrading and expansion of the Transmission and Distribution Systems as defined in the IRP.
The Distribution System planning criteria shall be based on Prudent Utility Practices and relevant international standards. The overriding principle is the responsibility of the Distribution Licensee to “maintain any installation, apparatus or premises related to its licence in such a state as to be able to provide a safe, adequate and efficient electrical service”.
The Distribution System shall be planned for a demand with a Power Factor between 0.90 capacitive and 0.90 inductive under Normal Conditions.
The Distribution Licensee, in collaboration with the Single Buyer and the System Operator, shall undertake interconnection studies whenever necessary, in particular to determine the interconnection requirements of any User System or Generation Plant. The studies include:
DC 3.4.1 Energy and Demand Forecasts: Users connected at MV shall provide their Energy and Demand forecasts for at least the following five years (monthly forecasts for the first year, annual for subsequent years).
DC 3.4.2 Distribution System Data: The Distribution Licensee shall make available to the Single Buyer and the System Operator all data relevant to the Distribution System, in particular transformers, power lines and Distributed Generation Units.
DC 3.4.3 User System Data: For LV connections: maximum power required and type of loads. For MV connections: Active/Reactive Power requirements, load type, maximum harmonic currents, details of cyclic load variations.
Section DC 4 of the Distribution Code is applicable to all existing or potential Distributed Generators connected to the LV or MV Distribution System. The Distribution Licensee is responsible for all aspects related to the interconnections of Distributed Generators, including information exchange, the connection process, technical design specifications, safety requirements and compliance monitoring with standards. The Distribution Licensee may refuse the connection of a Distributed Generating Unit if this threatens the security or quality of supply.
The Distribution Licensee shall produce a document (DG Grid Code) for each category of Distributed Generation, covering procedural aspects (connection process up to the Connection Agreement) and technical aspects (safety requirements, design, construction, testing, commissioning and administrative aspects). The DG Grid Code shall be approved by the Authority.
The technical aspects of the DG Grid Code shall contain at least:
A Generation Plant with a Registered Capacity greater than 4 MW but not exceeding 10 MW connected via a dedicated line to the 22 kV section of the Transmission System shall comply with the requirements applicable to MSDG 3.
DC 4.4.1 Feasibility: The feasibility of connecting a Distributed Generation Plant shall be confirmed by a Network Interconnection Impact Study, conducted by the Distribution Licensee, on a case-by-case basis.
DC 4.4.2 Connection Studies: For CEB SOLAR PHOTOVOLTAIC SCHEME (HOUSEHOLDS), applications are allocated to the relevant feeder. For MSDG 1/2/3, the Distribution Licensee and the Single Buyer determine the required network modifications by conducting the appropriate studies.
DC 4.4.3 Capacity Allocation: The allocation of capacity to feeders for Distributed Generators shall be carried out in accordance with rules and procedures approved by the Authority.
The integrity of the Distribution System and the security and quality of supply to existing Users shall not fall below the standard level due to the parallel (synchronised) operation of Distributed Generators. Parallel operation of the DGP is only permitted if authorised by the Distribution Licensee and the System Operator in accordance with applicable schemes and policies.
Distributed Generators shall provide the Distribution Licensee and the Single Buyer with information on the Generation Plant and the proposed interface arrangements. Required information includes in particular:
DC 4.7.1.1 Connection Arrangements: CEB SOLAR PHOTOVOLTAIC SCHEME (HOUSEHOLDS) connected at 230/400 V; MSDG 1 connected at 22 kV via dedicated transformer; MSDG 2 or MSDG 3 connected via 22 kV switchgear panel and interconnection step-up transformer.
DC 4.7.1.2 Interconnection Transformer: The MSDG 1/2/3 interconnection transformer shall be of vector group Dyn11 (Delta on Network side, star on DGP side). The delta winding on the Distribution System side: (i) does not disturb the earth fault protection of the substation; (ii) prevents triple harmonics from reaching the Network; (iii) isolates the DGP from voltage dips due to single-phase earth faults. Alternative vector groups may be used subject to the Distribution Licensee's approval.
DC 4.7.1.3 Earthing:
DC 4.7.1.4 Electromagnetic Emission and Immunity: The Distributed Generation System shall comply with the requirements of IEC 61000.
DC 4.7.1.5 Surge Withstand Capability: The interconnection installation shall have a surge withstand capability (oscillatory and fast transient) in accordance with IEC 62305-3 (test levels of 1.5 kV). The design of control systems shall meet or exceed the requirements of IEEE C37.90.
The coordination and selectivity of the Protection system shall be safeguarded. The Protection system shall provide protection against faults occurring on the Distribution System and the DGP's electrical installations (short-circuit, earth faults, overload) and prevent Islanding.
The Distributed Generator shall ensure that all its electrical installations are protected at all times. The DGP shall be protected against: overload, short-circuit, earth faults, overcurrent, abnormal voltages, abnormal frequencies, lightning and loss of mains (ROCOF and vector shift).
Distributed Generating Units shall not supply the Distribution System after the formation of a Power Island. The DGP shall be disconnected from the Distribution System within 0.5 seconds of the formation of a Power Island (loss of mains protection, Table 3).
Following a Protection-initiated disconnection, the DGP shall remain disconnected from the Network until the voltage and frequency at the Interconnection Boundary have remained within Normal Condition limits for at least 3 minutes. Automatic reconnection is only permitted when the disconnection was due to operating parameters being outside normal ranges.
The Distributed Generator shall provide and install automatic synchronisation equipment. A Synchronism Check Relay shall be provided on all generator circuit breakers and all other circuit breakers capable of connecting the DGP's installations to the Distribution System.
The inter-tripping scheme shall be designed and pre-wired so that the tripping of the interconnection feeder circuit breaker at the 22 kV Distribution System Substation causes the tripping of CB1. This scheme is wired but initially disabled for Registered Capacities up to 4 MW only.
Solar PV Power Plants: (1) During daylight hours, upon tripping of the 22 kV circuit breaker on fault, the System Control Engineer remotely opens CB1, which inter-trips CB2 and all other outgoing circuit breakers. After supply restoration, CB1 is remotely reclosed and the MSDG site contact reclosed. (2) At night, circuit breaker CB1 is not opened as there is no PV generation.
The "watchdog" function of the protection relay shall issue an alarm in the event of malfunction. For DGPs with a Registered Capacity greater than 1,000 kW, this alarm signal shall (if required) be transmitted to the Distribution System Substation via optical fibre or wireless communication.
For DGPs with a Registered Capacity greater than 500 kW, the Distributed Generator shall submit to the Distribution Licensee the appropriate settings for the grading and discrimination of the interconnection protection (22 kV circuit breaker on the Distribution System side) with upstream protection. The Distributed Generator shall also submit the DGP fault current contribution (three-phase and single-phase-to-earth).
In addition to the mandatory interlocking systems (IEC 62271-200), an appropriate interlocking mechanism shall prevent the mechanical closing of CB1 onto an energised busbar on the client side. For synchronous/asynchronous machines: (a) a "Dead Bus Live Line" synchronism check relay shall prevent the electrical/remote closing of CB1 if the 22 kV busbar is energised; (b) a synchronism check relay on all generator circuit breakers capable of connecting the DGP to the Network.
Distributed Generators shall notify the System Operator and the Distribution Licensee if their Generation Plant has a Black Start Capability (ability to restart the Generating Unit in the absence of Network supply).
DG electrical installations shall not cause excessive voltage excursions nor deviate from the range maintained by the System Operator. A DGP shall not produce excessive distortion of the sinusoidal voltage or current waveforms, and shall comply with DC 6.
The Distributed Generator shall carry out tests and pre-commissioning in accordance with relevant standards and keep written records of results. The Distribution Licensee has the right to require ad hoc tests (harmonic distortion levels, voltage rise, protection operation, fault investigations).
Testing and pre-commissioning of CEB SOLAR PHOTOVOLTAIC SCHEME (HOUSEHOLDS) and MSDG 1 installations shall be carried out by an Installer.
For Greenfield projects, the Distributed Generator shall submit the test procedures to the Distribution Licensee for approval at least 3 months before the planned Commercial Operation Date. Tests shall be carried out by a Registered Professional Engineer (MSDG 2) or Independent Engineer (MSDG 3).
The testing phase includes at least:
For solar PV Power Plants only: module string polarity, Voc and Isc, PV array insulation resistance. For wind power plants: vibration level, overspeed trip, yaw drive tests. The pre-commissioning phase (in the presence of the Distribution Licensee and the System Operator) includes: active power measurement tests, relay functional tests, 22 kV energisation, reactive power capacity, power quality (IEC 61400-21), anti-islanding test.
The Distributed Generator shall submit a Certificate of Installation signed by the Installer / RPE / IE. Upon compliance, the Distribution Licensee issues a Certificate of Compliance confirming that the installation complies with the Distribution Code and is fit for connection to the Distribution System.
Parallel operation with the Distribution System is not permitted for Standby Generators unless expressly agreed by the System Operator. Customers with Standby Generators shall ensure that any part of the installation supplied by the generator is first disconnected from the Distribution System. Warning signs shall be placed on LV and MV poles and transformers where a Standby Generator is connected.
In the event of non-compliance, the Distribution Licensee informs the Distributed Generator in writing of the discrepancies. The Distributed Generator has:
After this period, the Distribution Licensee is entitled to disconnect the Distributed Generator. Reconnection requires the Distribution Licensee to certify that the installation complies with the Distribution Code.
An online UPS is required to ensure that the protection, measurement, control and communication systems operate without interruption for at least 3 hours after loss of network supply. In the event of loss of the secure auxiliary supply, all 22 kV circuit breakers of the Distributed Generator shall be tripped. For DGPs with a Registered Capacity ≥ 1 MW, all communication equipment shall be supplied by a separate UPS.
Alarms and trips shall have local indication and, for DGPs with a Registered Capacity ≥ 1 MW, a set of potential-free contacts for downstream transmission to the Distribution System Substation. External indicator lamps shall be installed for DGPs with a Registered Capacity > 200 kW: red lamp = parallel operation; green lamp = isolated operation.
DGPs connected to the MV network with a Registered Capacity greater than 2 MW shall submit a Distributed Generation forecast to the Distribution Licensee and the System Operator in accordance with the requirements of SOC 4.2.4.
A DGP with a Registered Capacity > 1 MW shall submit its preventive maintenance plan to the System Operator each year. The Distribution Licensee shall communicate its maintenance plans to DGPs connected to the MV network at least one week before the planned action. No compensation applies for any loss of generation due to preventive and corrective maintenance on the Distribution System network.
DC 4.15.5.1 Fault Ride-Through (LVRT): The DGP shall remain connected to the Distribution System for phase voltage dips where the voltage measured at the Delivery Point remains above the voltage-duration profile curve (Figure 1 for synchronous/asynchronous machines, Figure 2 for Power Plants). In addition, the DGP shall provide Active Power in proportion to the retained voltage and maximise the reactive current injected into the Distribution System.
DC 4.15.5.2 Frequency Response: A DGP with a Registered Capacity ≥ 1 MW shall provide a power-frequency response in accordance with Figure 3 (power reduction above 50.5 Hz at 40 %/Hz; reconnection only when frequency returns to ≤ 50.5 Hz). Disconnection < 0.5 s if frequency > 52 Hz or < 47 Hz.
DC 4.15.5.3 Reactive Power Control: A DGP with a Registered Capacity ≥ 1 MW shall be equipped with mutually exclusive Reactive Power control functions: (a) Power Factor Control; or (b) Reactive Power Control. A voltage control mode may also be required on a case-by-case basis.
DC 4.15.5.4 Ramp Rate Limits: A DGP with a Registered Capacity ≥ 1 MW shall have a maximum ramp rate (up and down) equal to the Registered Capacity (MW) divided by 5 for 1-minute ramps. Ramp rate settings shall be approved by the System Operator before commissioning. For any subsequent changes, a minimum two-week notice is required.
A DGP shall be installed in accordance with the manufacturer's instructions. The Installer shall take into account: maximum demand, type of earthing system, nature of supply, external influences, compatibility/maintainability/accessibility, protection against electric shock and thermal effects, protection against overcurrents, isolation and switching. The Installer shall affix a label clearly indicating the next planned maintenance. The Installer shall be qualified in the field of DGP electrical installations and hold an approved certificate.
An MSDG 2 with a Registered Capacity ≥ 1 MW or MSDG 3 shall install communication equipment for the secure transfer of operational data and protection and control signals via: (a) optical fibre cables (DGPs with Registered Capacity ≥ 1 MW); (b) 4G/LTE (via VPN) or Microwave link as a backup communication channel. The Distributed Generator bears the cost of installing the communication from the DGP to the corresponding Substation.
Data to be transmitted includes:
Wireless communications (if used) shall use 3G/4G/LTE or newer technology, a Microwave link as the primary channel and 3G/4G/LTE as backup, dual-SIM capability, VPN tunnels, two routers in primary/hot-standby configuration, data rate ≥ 85 kbps downstream / 42 kbps upstream.
This section specifies the normal method of interconnection to the Distribution System and the minimum technical, design and operational criteria with which every User shall comply. All interconnection costs and responsibility are normally borne by the User connected to the Distribution System.
DC 5.4.1 Low Voltage Interconnections: Supply provided as single-phase 230 V or three-phase 400 V. Information required for LV interconnections includes at minimum: Customer name/address, location, type of interconnection, required capacity, identification of large motors or welding equipment.
DC 5.4.2 Medium Voltage Interconnection: Prior to the first energisation of a User System, the following data shall be provided to the Distribution Licensee: updated data, protection diagrams, Operating Diagram, list of Safety Coordinators, Common Site Plans.
Generator Interconnections shall comply with the relevant requirements of the Generation Code and Section DC 4. The operator of a Distributed Generation Plant shall operate and maintain Generating Units in a manner that does not adversely affect the Distribution System and other Users.
All Users connected to the Distribution System shall maintain the quality of the voltage waveform at the Interconnection Boundary within the limits specified in this section.
DC 6.2.1 Voltage: The Distribution Licensee shall limit line-to-neutral voltage harmonics below the values recommended in IEEE 519 for the Interconnection Boundaries of all Users (Table 4).
DC 6.2.2 Current:
DC 6.3.1 Voltage Flicker: In accordance with the maximum values at the Interconnection Boundary specified in IEC TR 61000-3-7 (MV) and IEC TR 61000-3 parts 3 and 11 (LV).
DC 6.3.2 Voltage Variations:
The weekly 95th percentile of Phase Imbalance (Voltage), calculated in accordance with IEC 61000-4-30 and IEC 61000-3-13, shall be ≤ 1.3 % on the Distribution System, except under abnormal conditions.
DC 6.5.1 Limitation of DC Injection: A Customer or Distributed Generator shall not inject a direct current greater than 0.25 % of the rated AC output current per phase. A Generator/Customer connected to the LV network shall not inject a DC current greater than the larger value between 20 mA and 0.25 % of the rated AC output current per phase.
DC 6.5.2 Voltage and Current Imbalance: The total voltage imbalance in the Network shall be less than 2 %. The contribution to the voltage imbalance level at the Interconnection Boundary of a Distributed Generation Plant shall be ≤ 1.3 %.
All electrical installations related to Users/Licensee at the Interconnection Boundary shall comply with the requirements of DC 7 and its sub-sections.
All circuit breakers, disconnectors, earthing devices, power transformers, voltage transformers, current transformers, surge arresters and other equipment at the Interconnection Site shall be constructed, installed and tested in accordance with the technical standards specified by the Distribution Licensee and Prudent Utility Practices. Installations and switchgear shall be designed, manufactured and tested in ISO 9001-certified or equivalent premises.
All protection systems and settings shall comply with the Distribution Licensee's Protection Policy. The protection of the Distribution System and Customers shall be designed, coordinated and tested to isolate affected parts of the System at the required speed and sensitivity, while maintaining supplies to the rest of the System. The Distribution Licensee alone is responsible for the protection of the Distribution System; Users alone are responsible for the protection of their Systems on their side of the Interconnection Boundary.
Responsibility for the construction, commissioning, control, operation and maintenance of Electrical Installations is determined according to the ownership of each installation, unless an agreement between the Parties provides otherwise.
The Distribution Licensee and all Users of the Distribution System shall comply with relevant electrical regulations. Prior to MV interconnection, the Distribution Licensee and the User shall conclude a written agreement on the Safety Rules to be used for works at Installations at the Interconnection Boundary (SOC 15).
A Site Responsibilities Table shall be produced for the System Operator and the Users with which it interfaces (format as per DC 21.1). These documents shall be included in the IA, ESPA, CA or PPA.
DC 8.4.1 Project Plans: The User shall prepare and submit 3 copies of all drawings to the Distribution Licensee and the System Operator for review (review within 15 days). Within 90 days of the Commercial Operation Date, the User shall provide a complete set of as-built drawings (2 paper copies and PDF electronic version).
DC 8.4.2 Operating Diagrams: An Operating Diagram shall be prepared by the User for each Interconnection Site in accordance with DC 21.2.
DC 8.4.3 Common Site Plans: The User prepares and submits the Common Site Plans for its side of the Interconnection Boundary. The Distribution Licensee then produces and distributes the complete Common Site Plans for the entire Interconnection Site.
Arrangements for access to Distribution Licensee sites by Users, and vice versa, shall be defined in each IA, ESPA, CA or PPA. The request shall be detailed and submitted 3 working days in advance.
For the purposes of this section, the term User refers to Distributed Generators and Customers connected to the MV Distribution System. Telecommunications between User(s) and the System Operator shall be established if required by the System Operator. Control telephony is the means by which Operations Engineers communicate for the control of the Distribution System, in both normal and emergency situations. The User shall install appropriate telephony equipment if its installation is not compatible with the Operator's system.
The System Operator shall provide a SCADA outstation interface. The User shall provide 4–20 mA measurement signals for voltage, current, frequency, Active Power and Reactive Power, as well as Equipment positions and alarms to the System Operator's SCADA outstation equipment (in accordance with DC 21.3).
In order to ensure that the Distribution System is operated efficiently and in accordance with Licence conditions, the Distribution Licensee with the support of the System Operator shall organise and carry out tests and/or monitoring of the effect of Users' Installations on the Distribution System.
The purpose of DC 10 is to specify the requirement for testing and/or monitoring in order to ensure that Users are not operating outside the technical parameters required by the Distribution Code.
The System Operator periodically determines the need to test and/or monitor power quality. These tests are carried out at the System Operator's expense. If a counter-test is requested by the User, it is carried out at the User's expense. A User operating outside the limits shall rectify the situation or disconnect the Equipment causing the problem immediately or within a timeframe agreed with the System Operator.
The System Operator periodically monitors the Active and Reactive Power flows at the Interconnection Boundary. All costs related to increasing the physical capacity of the Boundary are borne by the User.
The System Operator establishes requirements for Distribution System Users and Customers to enable reductions in total demand in the event of insufficient generation to meet total demand, or to avoid disconnecting Customers and Users, or in the event of a failure and/or overload on any part of the Transmission and/or Distribution Systems. Demand Control procedures aim to minimise difficulties for Users and to treat all affected parties equitably. The System Operator and Users shall comply with the requirements established in section SOC 9 of the System Operations Code.
The System Operator and Users shall exchange information so that the implications of an Operation and/or an Incident can be considered, potential risks assessed and appropriate actions taken to maintain the integrity of the Total System and Users' Installations. The System Operator and Users shall comply with the requirements established in section SOC 11 of the System Operations Code.
All System Installations and Equipment shall be operated and maintained in accordance with Prudent Utility Practices and in a manner that does not constitute a threat to the safety of employees or the public. The System Operator shall establish a Distribution System Maintenance Policy which shall be reviewed and approved by the Authority. The Distribution Licensee shall coordinate with the System Operator the planned maintenance of MV installations in the Distribution System. The System Operator, the Distribution Licensee and any connected User shall comply with the requirements established in section SOC 12 of the System Operations Code.
Medium Voltage switching shall only be carried out with the permission of the System Control Engineer or their designated representatives, except in the event of a System Emergency. Persons required to carry out Medium Voltage switching shall be specifically certified and authorised by the System Operator to perform such switching. The System Operator shall comply with the requirements and procedures of section SOC 7 of the System Operations Code.
This section defines the responsibilities and procedures for notifying the relevant owners of the numbering and nomenclature of Equipment at Interconnection Boundaries.
The main objective is to ensure that at any Site where there is an ownership boundary, each item of Equipment has a mutually agreed numbering and/or nomenclature, in order to ensure the safe and efficient Operation of the Systems involved and to reduce the risk of error.
New Equipment: The proposed numbering/nomenclature shall be notified in writing at least 3 months before the planned installation. The recipient shall respond in writing within one month of receipt.
Existing Equipment: The System Operator and each User are responsible for the provision and placement of clear labels indicating the numbering and nomenclature of their Equipment at sites having an Interconnection Boundary.
Modifications: When numbering/nomenclature needs to be changed, the same procedures apply. The party making the change is responsible for updating the labels.
This section defines the responsibilities and procedures for organising and conducting Special System Tests which have or may have an effect on the Distribution System or Users' Systems. Special Tests are those involving the simulated or controlled application of irregular, unusual or extreme conditions on the System, excluding commissioning or re-commissioning tests.
The objectives are: (a) to ensure that the procedures for organising Special Tests do not threaten the safety of personnel or the general public and cause minimum threat to the security of supplies and the integrity of Installations; and (b) to define the procedures to be followed for the establishment and reporting of Special System Tests.
When a User plans to undertake a Special System Test, notice shall be provided 1 month in advance to the Distribution Licensee and affected Users. The System Operator has overall coordination and convenes a Test Committee. The latter produces a proposal report within 2 months of its first meeting. If the report is unanimously approved by all recipients, a final test programme is submitted at least 1 month before the planned date. A final report is produced at the conclusion of the Test and the Committee is dissolved.
This section defines the manner in which power and energy flows shall be measured at an operational Interface. The Distribution Licensee is responsible for the acquisition, installation, maintenance, calibration and testing of meters and metering systems, as well as meter reading, billing and management of Customer complaints.
Required overall accuracy (maximum permissible values):
Parameters to be measured include: Active Energy (Wh) import/export, Reactive Energy (VARh) 1st and 4th quadrant, Active and Reactive Power demand and THD. The demand interval is 30 minutes. Measuring transformers shall comply with IEC 61869.
Required overall accuracy of billing metering systems: ± 1 % in laboratory and ± 2 % in the field. For CT meters: ± 1.5 % (LV) and ± 1 % (MV). All meters shall comply with the latest revisions of IEC 62053 or equivalent international standards.
For CT meters, the Delivery Point is at the position of the Current Transformers used for the metering system, designed as close as possible to the Interconnection Boundary. Current transformers shall be installed in a separate compartment, upstream of the main switch.
All meters shall be factory-calibrated. Calibration of electronic meters is carried out in the factory only. Any laboratory calibration shall be performed in laboratories accredited by the Mauritius Accreditation Service (MAURITAS). All meters shall be sealed to prevent unauthorised access, with an indication of the re-calibration date and serial number. The kilowatt-hour standard used for calibration shall be traceable to a recognised national or international standard. Only meters that have received type approval from the Mauritius Standards Bureau (MSB) may be used.
If the Metering System proves to be inaccurate by more than the permitted error and the Single Buyer and the Distributed Generator/User are unable to reach agreement within a reasonable time, the matter may be submitted to arbitration. A User/Distributed Generator has the right to request a verification of meter accuracy. If more than one verification is requested in the same calendar year, the Single Buyer may charge for the additional verifications if accuracy is within ± 2 %.
In general, the electrical system of the peripheral island of Rodrigues (a small isolated system comprising a few generators and 22 kV feeders) shall comply with the requirements of the Distribution Code, with the following exceptions.
The System Operator shall use Automatic Load Shedding by Under-Frequency Relays to handle short-term imbalances between Total System Power and Demand. The demand subject to automatic disconnection shall be divided into discrete MW blocks. After 2 activations, feeders at levels 1 and 2 shall where possible be exchanged with those at lower levels so as not to penalise the same Customers.
Each Generating Unit or Power Plant in Rodrigues shall be equipped with a fast-acting frequency control device (Governor Control System) with:
The purpose of DC 19 is to: (a) list all data to be provided by Users to the System Operator and the Single Buyer; (b) list all data to be provided by the System Operator to Users; and (c) list all data to be exchanged with Distributed Generators under the Distribution Code.
Each data item is classified into three categories:
Each User shall submit the data summarised in DC 20 to the Distribution Licensee, who then shares it with the Single Buyer and the System Operator. Data may be submitted via computer link, USB key, CD ROM or cloud technology, following prior written consent. The User shall notify the Distribution Licensee of any change to already submitted data. If a User does not provide the required data, the Distribution Licensee may estimate it in collaboration with the System Operator and/or the Single Buyer.
The following information is required from each User connected to the Distribution System via an Interconnection Boundary:
The following information is required from each User connected via an Interconnection Boundary where the User System contains one or more Distributed Generating Units and/or motor loads:
Each Site Responsibilities Table shall: clearly indicate the ownership and responsibility of each item of Equipment at the Interconnection Site; be signed on behalf of the System Operator and the User with date; be included in the IA, ESPA, CA or PPA. The standard form includes the fields: Company, Interconnection Site, signatures and dates of both parties.
Where possible, all MV Equipment at any Interconnection Site shall be represented on a single Operating Diagram. The layout shall represent as accurately as possible the geographical arrangement at the Interconnection Site. Operating Diagrams shall accurately show the current status of Equipment (in service/out of service). Items to be represented include in particular: busbars, circuit breakers, disconnectors and switches, earthing devices, power transformers, measuring transformers (current and voltage), surge arresters, black start generators. All graphical symbols used shall be approved by the System Operator.
General requirements for SCADA signals shall comply with IEC 60870-2-1 and IEC 60870-3 (electromagnetic compatibility). In particular:
DC 21.4.1 Typical MSDG 1 Interconnection Arrangement: The typical interconnection for MSDG 1 is described in this annex.
DC 21.4.2 Typical MV Switchgear Panel and Protection Guide for MSDG 2 and MSDG 3: Important notes include: